skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: A summary of the Fire Testing Program at the German HDR Test Facility

Technical Report ·
DOI:https://doi.org/10.2172/146789· OSTI ID:146789
 [1]
  1. Sandia National Labs., Albuquerque, NM (United States)

This report provides an overview of the fire safety experiments performed under the sponsorship of the German government in the containment building of the decommissioned pilot nuclear power plant known as HDR. This structure is a highly complex, multi-compartment, multi-level building which has been used as the test bed for a wide range of nuclear power plant operation safety experiments. These experiments have included numerous fire tests. Test fire fuel sources have included gas burners, wood cribs, oil pools, nozzle release oil fires, and cable in cable trays. A wide range of ventilation conditions including full natural ventilation, full forced ventilation, and combined natural and forced ventilation have been evaluated. During most of the tests, the fire products mixed freely with the full containment volume. Macro-scale building circulation patterns which were very sensitive to such factors as ventilation configuration were observed and characterized. Testing also included the evaluation of selective area pressurization schemes as a means of smoke control for emergency access and evacuation stairwells.

Research Organization:
US Nuclear Regulatory Commission (NRC), Washington, DC (United States). Div. of Engineering Technology; Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)
Sponsoring Organization:
Nuclear Regulatory Commission, Washington, DC (United States)
DOE Contract Number:
AC04-94AL85000
OSTI ID:
146789
Report Number(s):
NUREG/CR-6173; SAND-94-1795; ON: TI96002834; TRN: 96:001335
Resource Relation:
Other Information: PBD: Nov 1995
Country of Publication:
United States
Language:
English