1 Introduction

1.1 The potential of all glass columns

Large, column-free spaces have long fascinated architects worldwide as they allow for unobstructed views and space and light continuity. Nevertheless, the absence of columns in a building is often linked with expensive and complex structural solutions. Transparent columns, made of glass, could be a promising answer to this conflict between architecture and structural engineering. Revealed only by the play of light and of reflections, free-standing glass columns would disrupt the openness of a space the least while forming structural members capable of transferring vertical loads. Indeed, glass’s characteristic properties of transparency, durability and of a compressive strength up to \(1000\,\hbox {N}/\hbox {mm}^{2}\) (Saint Gobain 2016), exceeding that of wood, concrete and even steel (Granta Design Limited 2015), render it the most suitable candidate for realizing diaphanous compressive members. Nevertheless, despite the continuously ascending use of glass in structural components such as beams, portals, shear walls and self-carrying façades over the last decades, free-standing glass columns are still in a very early stage of development. This can be attributed to the insufficient knowledge regarding their structural behaviour and load carrying capacity under exceptional loading conditions (Kalamar et al. 2016).

Fig. 1
figure 1

The five different types of all glass columns as described by Nijsse and ten Brincke (2014)

Table 1 Geometrical and mechanical properties of characteristic examples of the five types of free-standing columns as stated in literature

1.2 Previous examples of all glass columns

To the knowledge of the authors, at present, glass profile columns of a cruciform (X) cross-section are the only type of free-standing glass columns applied in buildings. The first realized example, built in 1994 in St-Germain-en-Laye in France, comprises eight 3.2 m high cruciform glass columns that support a glass patio. The cruciform profile was selected due to its increased resistance to buckling (Schittich et al. 2007). The same typology of columns was later followed at the Danfoss Headquarters in Denmark, where twelve 5.5 m high cruciform columns support the reception building (Petersen and Bagger 2009). The inclusion of the columns was only possible after performing 1:1 scale loading tests in which the components demonstrated the ability to carry much higher compressive forces than required. Specifically, the columns applied in the St-Germain-en-Laye office could withstand a force equal to approximately 6 times the calculated maximum load (Nijsse 2003). A series of structural experiments on a full-scale specimen for the Danfoss headquarters proved that even after the column is severely damaged from hard impact under loading, it can still carry an axial load greater than twice the expected maximum force (Petersen and Bagger 2009). Thus, in both examples, the tested columns present a safety factor >2. Still, due to the unpredictable and sudden failure of glass, in both cases, the roof is designed with sufficient redundancy to redistribute the forces in case one or more glass columns fail in a complete way (Petersen and Bagger 2009; Nijsse 2003). These two case studies exhibit both the potential and the engineering constraints of all glass columns. Despite having more than adequate load-bearing capacity, the application of glass columns in buildings is linked with increased safety factors compared to standard materials, as well as with the design of alternative load paths to compensate for the lack of a built-in safety system.

Beside these two examples, other configurations of free-standing glass columns have, at present, only been explored within research context and tested in lengths typically restricted to 1.5 m. Exploring the possibilities, (Nijsse and ten Brincke 2014) introduce the following five design concepts of free-standing all-glass columns, illustrated in Fig.1: profile, layered tubular, stacked, cast, and bundled. Table 1 summarizes the geometrical and mechanical properties of characteristic samples of the five column types described in this section.

Alternative configurations of profile columns, i.e. H, T, X and square profiles, and their compressive behaviour have been explored experimentally, numerically and analytically by Ouwerkerk (2011), Aiello et al. (2011), Campione and Rondello (2014), Overend et al. (2005) and Kalamar et al. (2016). The findings demonstrate that the 3-dimensional geometry of such glass columns results in an increased structural resistance and stiffness. Most importantly, they manifest that the adhesive connections between the glass elements are of crucial importance to the overall performance. Research and experimental work has been conducted on tubular columns by Achenbach and Jung (2003), Overend et al. (2005), Nieuwenhuijzen et al. (2005) and Veer and Pastunink (1999). Actually, glass tubes have been previously structurally applied but not in the form of columns, with the most characteristic examples being tensegrity structures by the University of Stuttgart (Achenbach et al. 2002) and the glass atrium façade of the Tower Place office building in London (Doenitz et al. 2003). In the latter, the approx. 40 glass tubes that transfer the wind forces to the primary load-bearing system, consist of a core tube laminated to a split tube functioning as an external protecting shell and have a built-in steel cable system. In contrast, the developed column by Nieuwenhuijzen et al. (2005) and Veer and Pastunink (1999) consists of two concentric glass tubes, laminated together by a clear low-shrinkage resin, aiming on utilizing structurally the entire glass composition. This production process, however, involved several practical implications due the adhesive’s shrinkage and the dimensional intolerances of the glass tubes. A horizontally stacked, translucent, column made of float glass panels bonded together by an adhesive film has been explored by Van Heugten (2013) and Felekou (2016). Cast and bundled glass columns are until now the least explored options. In theory, cast glass columns could form the ideal solution for transparent load-bearing components. Through casting, monolithic, entirely transparent structural glass members of the desired form and cross-section could be materialized. However, casting glass in such large volumes requires a precise and excessively time-consuming cooling process that renders the manufacturing of storey-high glass columns cost- and time-inefficient. This can be well illustrated by the “Opposites of white” cast sculptures by artist Roni Horn. Each drum-shaped sculpture, 50.8 cm high by 142 cm diameter, required 4 months of controlled annealing to prevent the generation of residual stresses (Kroller-Muller Museum 2007). The even larger glass mirror of Hale-1 telescope, following a honeycomb structure and measuring 5 m in diameter and 0.66 m in thickness, required 10 months of annealing (Corning Museum of Glass 2011). To overcome the practical limitations involved, the concept of a dry-assembly column consisting of interlocking, vertically stacked, cast glass units of max. 10 kg mass was developed by Akerboom (2016). A similar concept of glass columns consisting of adhesively bonded cast glass bricks has been tested by Oikonomopoulou et al. (2015b) and Felekou (2016).

Fig. 2
figure 2

Realized 1.5 m long prototypes of the bundled glass column

Fig. 3
figure 3

Left CONTURAX\(^{{\textregistered }}\) and DURAN\(^{{\textregistered }}\) profiles. Right Concluded configuration of the bundled glass column

The bundled column (see Fig. 2) is the fifth type of column, defined by Nijsse (2003) as a safe, all glass column made of a bundle of solid glass bars that are adhesively bonded together. This column concept was first conceived for the ABT Office in Arnhem: 7 glass solid rods of 30 mm diameter each, in a configuration where the central one is surrounded by the other six, were to be bonded together by a transparent UV-activated glue that would prevent the buckling of each bar individually (Nijsse 2003). Nevertheless, this column was never realized, due to the difficulty in establishing a bonding method and a rod configuration that could ensure consistent results of the desired visual and structural performance. Little experimental data exist so far regarding this type of column. These concern an investigation on the structural performance of a bundle consisting of three hollow glass tubes bonded together by a low modulus structural silicone conducted by Kamarudin et al. (2016). Nevertheless, this research does not address the attained optical result when bonding the tubes with this method.

1.3 Realizing the bundled glass column

This paper presents the research and experimental testing and discusses the feasibility of the fifth type of glass columns, the bundled. This alternative has not been explored in depth until now even though it presents great prospects in terms of fabrication, visual result and structural performance. In this work, a production method for constructing bundled glass columns on a scale relevant to buildings is first described, analysing the practical limitations and proposed solutions. Following, series of prototypes in different scales are made and tested in compression and the results are discussed in terms of structural performance. Lastly, in an attempt to introduce a more gradual and visible buckling failure the concept of post-tensioning is introduced to full-scale specimens and experimentally evaluated. Based on the findings, suggestions are made for further engineering the bundled column.

2 Design concept and production considerations

The concept of the bundled column is simple. Multiple glass bars are bonded together by a colourless adhesive, forming a composite yet integral cross-section. In terms of visual performance, the bundled glass column is transparent, yet not invisible. The curved geometry of the rods generates playful distortions and light reflections, subtly revealing the existence of the column (Oikonomopoulou et al. 2016). The column’s load-carrying capacity is enhanced by the symmetrical cross-section of both the rods and the composite shape. Solid rods of a circular cross-section from the DURAN® series by Schott are selected due to their inherent resistance in buckling and torsion. These are standardized, extruded borosilicate glass rod profiles, 1500 mm in length, with diameters ranging from 3(±0.14) to 30(±0.80) mm (SCHOTT 2012). To create a symmetrical bundle, a configuration comprising seven extruded profiles, a central one surrounded by six external ones, is further examined. Initially, different fabrication methods comprising seven rods of identical circular cross-section were explored. Such a rod arrangement proved incapable of guarantying a consistent visual and structural result, due to its inability to account for the standard diameter deviation of the rods and the visible distortions caused by the adhesive lines (Oikonomopoulou et al. 2016). A new configuration was proposed, consisting of a central hollow star-shaped CONTURAX\(^{{\textregistered }}\) profile and six external DURAN\(^{{\textregistered }}\) rods with a diameter corresponding to the convex of the flutes of the central star profile. The CONTURAX\(^{{\textregistered }}\) profile is commercially only available with a 17(±2.00) mm inner and 30(±2.00) mm external diameter (SCHOTT AG 2013). To match the central profile’s curvature, the six external DURAN\(^{{\textregistered }}\) rods have a diameter of 22(±0.45) mm (see Fig. 3). The construction of several prototypes proved that the matching curvature between the surface of the rods and the flutes of the central profile allows for consistent bonding stripes of a high visual result, despite the tolerances in the size of the individual components (Oikonomopoulou et al. 2016).

The adhesive connection between adjacent glass components plays a key role in the overall structural performance of glass columns (Kalamar et al. 2016). Thus, the degree of mechanical collaboration between the rods is highly dependent on the applied adhesive. The higher the bonding strength, the more the adjacent elements couple, preventing individual buckling. Delo Photobond 4468, a one-component, clear, UV-curing acrylate, was selected for bonding the elements together due to its colourless nature, similar refraction index to glass, fast application and very good mechanical properties (Delo Industrial Adhesives 2014). The specific adhesive was also applied in the construction of the Crystal Houses façade in Amsterdam (Oikonomopoulou et al. 2017). 4-point bending experiments on glass beams consisting of adhesively bonded solid glass bricks by Oikonomopoulou et al. (2015a) demonstrated the monolithic behaviour of the glass-adhesive assembly under loading.

3 Fabrication of the prototypes: materials and methods

3.1 Overview of specimens

Based on the proposed manufacturing method, series of specimens in different scales are made and experimentally tested in compression. Figure 4 shows an illustration of the series of prototypes and Table 2 summarizes their geometrical characteristics and boundary conditions.

Fig. 4
figure 4

Illustration of all specimen series tested in compression

Table 2 Overview of the specimens’ characteristics

Compression testing is initially carried out on series of small prototypes [\(\hbox {A}_{1}\) and \(\hbox {A}_{2}\)] to evaluate the degree of coupling between the rods when bonded with the selected adhesive, as well as the influence of spliced connections along the length of the rods. For this purpose, the results of these series will be discussed separately in Sect. 4, since they are used as the basis for the fabrication of longer specimens. Following, series of specimens in a scale relevant to buildings [\(\hbox {B}_{1}\) and \(\hbox {B}_{2}\)] are tested in compression until failure and the results are discussed in terms of load-carrying capacity and failure behaviour. Finally, a series of prototypes with an introduced axial post-tensioned steel tendon [\(\hbox {C}_{1}\)] is built and tested in compression with the aim of attaining a more gradual and visible buckling failure.

3.2 Production method of the glass bundle

Based on the findings of Sect. 2, each specimen consists of a central hollow star-shaped CONTURAX® borosilicate glass profile with 17(±2.00) mm inner and 30(±2.00) mm external diameter adhesively bonded to 6 borosilicate DURAX® rods of Ø 22(±0.45) mm, which form the external bundle (see Fig. 5).

The rods are bonded one by one in a horizontal position to the flutes of the central profile along their length, in a strip approx. 8 mm wide, by Delo Photobond 4468 adhesive. The latter is fully cured during a minimum of 40 s using 60 mW/cm\(^{2}\) UVA intensity (Delo Industrial Adhesives 2014). An illustration of the bonding method can be seen in Fig. 6.

Fig. 5
figure 5

The bundled column cross-section

Fig. 6
figure 6

Schematic illustration of the bonding method applied to the glass bundle. From left to right The rods are individually bonded to the flutes of the central profile in a horizontal position and cured by a UV-lamp travelling back and forth along its length. The process is repeated for each rod until the bundle is complete

All glass profiles used are properly annealed in Schott’s premises. Each profile is carefully cut to size using a diamond blade saw and its ends are manually ground. Once the profiles are bonded together and the bundle is formed, the top and bottom surfaces are manually ground again carefully to remove any protrusions due to misalignment or difference in length of the individual rods and to obtain a flat surface perpendicular to the axis.

3.3 End connections of specimens

3.3.1 Clamped connections of specimen series \(\mathrm{A}_{1}\), \(\mathrm{A}_{2}\) and \(\mathrm{B}_{1}\)

Specimens \(\hbox {A}_{1}\), \(\hbox {A}_{2}\) and \(\hbox {B}_{1 }\) are tested while establishing clamped connections in the testing machine, as such: At both ends of the bonded glass bundle two milled aluminium caps are mounted to form the top and bottom bases (see Fig. 7). The caps, besides stabilizing the bundle, prevent direct contact between the glass and the steel surface of the testing machine. Prior to mounting, a soft, 1 mm thick sheet of lead is placed inside each aluminium head (see Fig. 7). This yielding interlayer allows for the even distribution of the applied compression load, preventing peak stress concentrations due to possible unevenness in the glass’ contact surface. The connection between the aluminium cap, coated with the inlayed lead, and the glass bundle is realized by a clear adhesive. In specific, once the column is aligned to be in the centre of the aluminium head, a two-component clear polyurethane is carefully mixed and poured in between the glass and aluminium at the ground base to create a rigid head. Crystal Clear\(^{{\textregistered }}\) 200 resin is chosen due to its water and UV- resistance and negligible shrinkage (SMOOTH-ON 2016). This resin is left to cure for a minimum of 16 h. Then the column is flipped and the other side is treated the same way.

Fig. 7
figure 7

The aluminium cap with the inlayed lead sheet and a section of the glass bundle

Fig. 8
figure 8

Top (left) and bottom (right) pinned connections of the experimental set-up of the \(\hbox {B}_{2}\) specimen series

Fig. 9
figure 9

Left Position of the steel tendon and PVC tube at the post-tensioned specimens. Right The steel cap detail

3.3.2 Pinned connections of specimen series \(\hbox {B}_{2}\)

In specimen series \(\hbox {B}_{2 }\) the same aluminium cap connections are applied, yet an addition is made to the detail so that the columns are tested in a pinned configuration. Specifically, a steel cap with a milled convex and a corresponding half-sphere steel component is placed under the base aluminium cap (see Fig. 8). For the top connection the same detail is applied above the top aluminium cap, by an identical steel cap welded to the steel surface of the testing machine (see Fig. 8). Prior to testing, the complete specimen is stabilized by restraining the height of the column through carefully adjusting the machine’s top pressing plate so that contact is made. The force introduced before the experiment starts is negligible.

Fig. 10
figure 10

Illustration of the post-tensioned glass column head detail

3.3.3 Pinned connections of specimen series \(\hbox {C}_{1}\) and application of the post-tensioning

The production process for the \(\hbox {C}_{1, }\) post-tensioned variant of 2400 mm length, is identical to the \(\hbox {B}_{2}\) series of prototypes with the exception of the post-tensioning tendon and the use of steel top and bottom caps. The hollow core of the central star-shaped CONTURAX\(^{{\textregistered }}\) borosilicate glass profile, of 17(±2.00) mm diameter, is used to accommodate the post-tensioning tendon. To account for the ±2.00 mm production tolerance in the inner diameter of this profile, a standardized M12 threaded rod is used as tendon with PVC tubing, of 16mm outer and 13.6 mm inner diameter, around it, to prevent direct contact between the steel and the glass (see Fig. 9). Due to the inevitable production tolerances of the CONTURAX® profile, the PVC-coated tendon is not in direct contact with the glass, but as close to glass as possible using stock materials.

Pre-stress applied to a tendon is dependent on the type of steel. Although material properties vary, an approximate estimate of proof strength is 85–90% of its yield strength (Shigley and Mitchell 1993). Using 8.8 bolt quality steel the torque value that can be safely applied is 80(±10) Nm, which translates to roughly 35 kN of axial force.Footnote 1 The post-tensioning is applied using a Stahlwille 730/10 torque wrench with corresponding square drive which allows for a maximum torque application of 100 Nm.

In contrast to all previous specimens, the post-tensioned columns heads are made of the same 8.8 quality steel as the post-tensioning tendon, nut and washer (see Fig. 9) for better cooperation of the components. The bottom steel cap has an axial hole with a female M12 thread in which the post-tensioned tendon can be fixed. The top steel cap has a 13 mm hole to allow free passage of the tendon, which is tightened with a M12 washer and nut using the torque wrench (see Fig. 10). In these steel heads a 1 mm thick layer of lead is again used as intermediary to prevent direct contact between the glass column and the steel heads. The same pinned connection details between steel caps and testing machine are applied, as described in the \(\hbox {B}_{2}\) specimens.

Fig. 11
figure 11

Experimental set-up of A\(_1\) specimens

Table 3 Dimensions and failure stress values of the A1 specimen series

4 Testing of \(\hbox {A}_{1}\) and \(\hbox {A}_{2}\) series: initial evaluation of the coupling degree between the rods and the influence of spliced connections

Prior to the production of longer specimens it was essential to evaluate the degree of coupling between the rods when bonded with the selected adhesive, as well as the influence of spliced connections necessary for the fabrication of prototypes exceeding the standardized rod length of 1500 mm. Therefore, two series of small scale prototypes, namely \(\hbox {A}_{1}\) and \(\hbox {A}_{2}\), were made and tested under compression to evaluate each of the two parameters respectively. These tests and their results are presented below.

4.1 Testing of \(\hbox {A}_{1}\) series: evaluation of the degree of coupling of the rods

To examine the degree of coupling between the individual rods, compression tests were conducted at the A\(_{1}\) series of prototypes of 500 mm length. The experimental set-up can be seen in Fig. 11. Table 3 summarizes the dimensions, failure load and corresponding nominal compressive stress of the three tested specimens.

All specimens failed in a sudden and complete way at a consistent compressive stress of approximately 500 MPa. The high failure stress indicates that, owing to the lead sheet insert, edge flaws and unevenness on the length of the individual glass rods have a minor influence, if any at all, to the total load-carrying capacity. Most importantly, the consistency and magnitude of the failure stress values suggest that either the compressive strength of glassFootnote 2 or the compressive shear strength of the adhesive have been reached. In either case, it is safe to assume that the high shear stiffness of the selected adhesive enables the bundle to behave as a single monolithic unit under a compressive force less than 1000 kN.

4.2 Testing of A\(_{2}\) series: evaluation of the influence of spliced connections

According to SCHOTT AG (2017), the maximum manufacturing length in extruded profiles is 10 m, sufficient for realizing even three-storey high columns. Nevertheless, in practice, Schott’s extruded profiles are standardized up to 1500 mm length. Communication with the manufacturer suggested that longer profiles can be produced only for orders exceeding 500 U. Due to cost restrictions such an order was not possible. Hence, to produce specimens applicable in a building scale, a configuration similar to the splice-lamination principle was applied. Specifically, the column is segmented so that the connection points spiral up along its height. In this way, the generation of weaker zones is minimized. To optimize the material use of the standardized 1500 mm rods, every split point of the spiral, splice-lamination is in 250 mm absolute height distance from the split point of the adjacent rod. An illustration of this scheme is given in Fig. 12.

Fig. 12
figure 12

Splice-lamination scheme of specimens \(\hbox {B}_{2}\) and \(\hbox {C}_{1}\)

Fig. 13
figure 13

Left Specimens for testing. Center detail of the aluminium disc spliced joint. Right Experimental set-up

The influence of three alternative connection types, each 2 mm thick, to the column’s carrying capacity is further evaluated by the experimental testing of the \(\hbox {A}_{2}\) series of prototypes: an empty gap, a gap filled with Delo Photobond 4494 adhesive and an aluminium ring connection. Delo Photobond 4494 is opted due to its compatibility with Delo Photobond 4468, its good mechanical properties (Delo Industrial Adhesives 2016), medium viscosity and ability to form a 2 mm thick joint.Footnote 3 Aluminium (bonded with Delo Photobond 4468 to the glass surfaces) is chosen due to its comparable to glass, yet slightly lower, Young’s Modulus. A series of three 470 mm high specimens consisting each of 3 adhesively bonded rods of Ø 22(±0.45) mm, where one is interrupted in the middle (see Fig. 13) are made for each connection type and tested until failure in a displacement controlled hydraulic compression machine with a 1 mm/min rate of loading. The results of each series, summarized in Fig. 14, are compared to the structural performance of a series of identical specimens comprising monolithic, undisrupted rods.

Specimens failed under forces ranging between 95 kN and 277 kN.Footnote 4 Figure 14 clearly indicates that the specimens with aluminium disc connections are mechanically the closest to the monolithic variant. From the results it can be derived that aluminium performs at approx. 85% of the full glass sample. In comparison, the adhesive connection performs at roughly 55% of the benchmark and the empty gap at 35%. Therefore, in this work, for the fabrication of the 2400 mm long specimens of the \(\hbox {B}_{2}\) and \(\hbox {C}_{1}\) series aluminium disks are selected for the split connectors between rods (see Fig. 15).

Fig. 14
figure 14

Carrying capacity of the \(\hbox {A}_{2}\) specimens with alternative connection types: Empty: 1–3, Adhesive connection: 4–6, Aluminium connection: 7–9, Monolithic rods: 10–12

Fig. 15
figure 15

Right Prototypes of the \(\hbox {B}_{2 }\)series using the spliced lamination principle in a spiral configuration, seen on the left

5 Compression testing on series \(\hbox {B}_{1}\), \(\hbox {B}_{2}\) and \(\hbox {C}_{1}\)

The structural performance and failure behaviour of the designed bundled column is evaluated through compression tests until complete failure on a series of clamped specimens of 1500 mm length [\(\hbox {B}_{1}\)], pinned specimens of 2400 mm length [\(\hbox {B}_{2}\)], and pinned post-tensioned specimens of 2400 mm length [\(\hbox {C}_{1}\)], using a force-controlled hydraulic compression machine (see Fig. 16). There are three identical specimens for each series. The production of the prototypes has been thoroughly described in Sect. 3.

Fig. 16
figure 16

Left Experimental set-up for the \(\hbox {B}_{1}\) series (clamped). Right Experimental set-up for the \(\hbox {B}_{2}\) series (pinned)

In the case of the \(\hbox {B}_{1}\) specimens, the available standardized 1500 mm length of the rods allows for a continuous bundle, sparing the necessity of splicing rods. The top and bottom aluminium caps are in direct contact with the steel surface of the testing machine and thus are expected to behave as clamped connections.

The longer specimens of the \(\hbox {B}_{2 }\) and \(\hbox {C}_{1 }\)series consist of the same rod configuration as the \(\hbox {B}_{1}\) prototypes, yet they follow a spiral, splice-lamination scheme. Based on the findings of the testing described in Sect. 4.2, 2 mm thick aluminium disks bonded with Delo Photobond 4468 to the rods form the split connectors.

The \(\hbox {B}_{2 }\) and \(\hbox {C}_{1 }\) specimens are tested in compression in a set-up with pinned top and bottom supports. For safety reasons, during testing, all specimens are surrounded by a wooden safety cage with a polycarbonate window.

6 Discussion of the experimental results

The results of the compression tests in \(\hbox {B}_{1}\), \(\hbox {B}_{2}\) and \(\hbox {C}_{1}\) specimen series are summarized in Table 4.

Table 4 Dimensions and strength values of B\(_1\), B\(_2\) and C\(_1\) series of specimens

The maximum nominal compressive stress (\({\upsigma }_{\mathrm{max}})\) of each specimen is calculated according to Eq. (1).

$$\begin{aligned} \sigma _{max} =\frac{F_{max} }{A} \end{aligned}$$
(1)

where F\(_{\mathrm{max}}\) is the maximum normal force applied perpendicular to the glass bundle’s cross-sectional area A.

The critical force for buckling (F\(_{\mathrm{cr}})\) for each column series is calculated based on Euler’s formula. Tests carried out on the \(\hbox {A}_{1}\) specimens (see Sect. 4.1) suggest that the selected adhesive allows the bundle to behave monolithically until a compressive load equivalent to at least 1000 kN. It is expected that the longer specimens, due to their high slenderness, will fail due to buckling at considerably lower force. Accordingly, the bundle can be assumed to be monolithic and the influence of the adhesive layer can be neglected for the determination of the critical buckling force (F\(_{\mathrm{cr}})\) using Euler’s buckling formula, seen in Eq. (2).

$$\begin{aligned} F_{cr} =\frac{\pi ^{2}EI}{\left( {KL} \right) ^{2}} \end{aligned}$$
(2)
Table 5 Material and geometry properties of the glass bundle
Fig. 17
figure 17

Load-displacement diagram of the \(\hbox {B}_{1}\) specimens

where, E is the modulus of Elasticity, I is the stiffness of the column about the axis it will buckle, typically the minor for asymmetric columns, L is the height of column and K is a factor accounting for the end conditions. In the case of both ends pinned, K is equal to 1.0, whereas for both ends clamped it is 0.5. Table 5 summarizes the parameters applied in the calculations, based on the material properties and geometry of the chosen glass profiles. The cross-sectional area and moment of inertia of the specimens are calculated based on the standard profile dimensions. The deviation in area due to manufacturing tolerances is considered of negligible influence to the ultimate stress and load values.

The slenderness ratio (\({\uplambda })\) of each specimen series has been calculated as the ratio of the effective length of the column to the least radius of gyration (r) of its cross section based on Eq. (3).

$$\begin{aligned} \lambda =\frac{K L}{r}, \end{aligned}$$
(3)

Based on data regarding the slenderness ratio of several experimentally tested glass columns, Kamarudin et al. (2016) concludes that glass columns with a slenderness ratio >40 can be classified as slender and are expected to fail due to flexural buckling. Indeed, all three series of specimens failed by buckling at their middle zone, as was anticipated, since their slender proportions result in tensile forces arising from the buckling deformations and out of plane bending that typically prevail (O’ Regan 2014).

In the \(\hbox {B}_{1}\) series of prototypes initial cracking was observed in loads significantly lower than their maximum load-carrying capacity, which ranged between 130–199 MPa. In specific, specimen 2 cracked at 260 kN and reached a maximum load of 389 kN; a load almost 1.5 times higher than the one causing the initial cracking. Specimen 3 initially cracked at 120 kN and failed under a load more than 4 times as high (508 kN). When reaching their maximum load all prototypes shattered suddenly in small pieces without maintaining any post-breakage carrying capacity. The load-displacement diagram of the three specimens of the \(\hbox {B}_{1}\) series is seen in Fig. 17.

Fig. 18
figure 18

Left Indicative load-displacement diagram of the \(\hbox {B}_{2 }\) specimens. Only the data of one specimen (indicated by the continuous line) were accurately recorded by the compressing machine. The failure of the other two specimens (indicated by dotted lines) is indicated here based on the observations and failure load recorded during testing. Right Load-displacement diagram of the \(\hbox {C}_{1 }\) specimens with post-tensioning. In both diagrams: 1 setting of the machine, 2 column is slightly compressed, 3 area where the lead layer is compressed, 4 column is loaded in compression, 5 initiaton of buckling

Based on the Eq. (2) the expected buckling force for the B\(_1\), 1500 mm long specimens assuming a clamped configuration was estimated to be 722 kN. This value exceeds considerably the maximum load the specimens could actually carry and cannot be solely attributed to induced eccentricities or flaws during the production of the specimens. A critical factor for the total carrying capacity are the end conditions of the specimen. Although the specimens were considered clamped in this series, each bundle was only kept in position by the pressure of the machine heads. Hence, it is possible that the large deviation between estimated and measured critical load is due to insufficient restrain at the clamped connections. It is probable that the aluminium caps started to twist during testing and functioned in between a pinned and a clamped connection. Indeed, if assuming connections are pinned, the specimens would be expected to start buckling at a significantly lower load of 177 kN. In these tests, the specimens failed between 330 and 508 kN, a range lying between clamped and pinned boundary conditions.

In the case of \(\hbox {B}_{2 }\) and \(\hbox {C}_{1}\) specimens, where the pinned top and bottom connections were realized more accurately, all specimens failed close to the theoretical critical buckling force of 70.5 kN. The influence of the spliced joints and of eccentricities during fabrication seems to have only a minor influence on the obtained stresses. Specifically, the \(\hbox {B}_{2}\) specimens failed by buckling in a complete way in a load range between 63 and 90 kN (see left diagram of Fig. 18). In two specimens, initial cracking was observed in a force approx. 20 kN less than the failure load.

In comparison, the post-tensioned \(\hbox {C}_{1}\) specimens failed in a lower load range, yet with significantly narrower spread, between 62.7 and 69 kN and visible buckling, as it can be seen on the right diagram of Fig. 18.

The consistency of the values and the relatively ductile failure mode can be attributed to the integration of the post-tensioned steel tendon. The post-tensioning seems to have successfully prevented initial crack propagation due to surface defects, resulting in more consistent results. Indeed, no significant cracking was observed in these specimens prior to failure. Also, it can be seen in Fig. 18 that the \(\hbox {C}_{1}\) specimens demonstrate a relatively ductile behaviour and considerably greater deformations compared to the non-post-tensioned variant, providing warning prior to failure. When the column finally fails as a result of buckling, only the glass on one side of the column breaks away. The glass on the compressive side of the buckling failure is held in place by the post-tensioning tendon (see Fig. 19). The column also maintains a limited load-carrying capacity, attributed mainly to the tendon’s tensile capability. In general, the ability of the column to withstand complete failure (see Fig. 20) and the consistent failure values result in an increased structural reliability which allows reduction of the imposed safety factors that generally apply to such glass structural members.

Fig. 19
figure 19

Left Failure pattern of a specimen of the \(\hbox {B}_{2 }\) series. Right Failure pattern of a specimen of the \(\hbox {C}_{1 }\) series

Fig. 20
figure 20

Characteristic failure of a prototype from the \(\hbox {B}_{2}\) (left) and the \(\hbox {C}_{1}\) (right) series

In an ideal scenario, where the tendon and the glass would fully cooperate, the tendon would postpone initial buckling as it would prevent the glass from moving away from the neutral axis; as a result it should fail in a higher load compared to the non-post-tensioned variant. The latter did not occur due to insufficient co-operation between the glass bundle and the steel tendon because of the inevitable manufacturing tolerances of the rods. The American Concrete Institute (2004) states in ACI-318-5 building code regarding the application of pre-stress on structural members, that a structural member cannot buckle under pre-stress applied if the post-tensioned tendon is in direct contact with the member or in sheathing not excessively larger than the tendon. Even though this code is generally applied to concrete members, the mechanical effect applies to structural members regardless of the material used. The tolerance of at least 1 mm between the tendon and the glass bundle in our case prevented the full-collaboration between the two elements. Instead, the glass was free to start moving away from the neutral axis of the column once the critical buckling force was reached. At that time, even though the tendon remained in the neutral axis, it was unable to prevent the initiation of buckling. Therefore, due to this relevant movement, the pre-stress applied through the tendon seems to have contributed to the critical buckling force, resulting in a seemingly lower failure load. Indeed, it can be seen at Fig. 18 that buckling is already triggered at a load of approx. 45 kN. If this is the case, and the pre-stress contributes to the compressive force, the specimens actually resist an overall higher compressive load than that of the non-post-tensioned variant. It is expected that optimizing the tendon configuration will result in higher failure loads as the tendon will then be in tight contact with the sheathing, constraining the lateral movement of the glass towards eccentricity. Since the manufacturing tolerances of the central glass profile cannot be improved, the application of a heat shrink plastic tube of sufficient stiffness prior to the assembly and post-tensioning on a tendon of the closest diameter to the glass profile hole can significantly contribute to the cooperation of the different components of the column. In this way, the overall tolerance between the glass and the plastic-coated tendon can be confined to a few decimals of a millimetre.

7 Conclusions and discussion

A completely transparent, bundled glass column has been developed and physically tested towards the evaluation of its feasibility. The results indicate that the bundled glass column can be an elegant solution of sufficient compressive strength in the search of a transparent, load-bearing component.

The experimental data from the compressive testing of small-scale specimens suggest that the described bundled column behaves monolithically under loading when the selected adhesive is applied. The consistent high failure stresses of these specimens indicate that the soft lead interlayer can eliminate the effect of induced imperfections in the contact surface as well.

The latter also highlights the importance of proper detailing of the column’s top and bottom connections for the estimation of the corresponding ultimate stresses. The load-carrying capacity of the specimen series \(\hbox {B}_{2}\) and \(\hbox {C}_{1}\) using accurately designed pinned connections proved to be within close proximity of the expected theoretical critical buckling force, assuming a monolithic glass bundle. In comparison, the carrying capacity of the \(\hbox {B}_{1}\) specimens that were clamped to the machine only by friction resulted in a critical force corresponding to a column configuration between a clamped and pinned situation.

Fluctuations of the load, variability of the material properties, eccentricities caused during production and uncertainties regarding the analytical models all contribute to lowering the probability of flawless behaviour. Still, the effect of the spliced joints using aluminium discs seems to have little influence on the final results. The performance could be further enhanced by applying monolithic rods of the desired length, or by forming longer members by welding the borosilicate rods together. Experimental testing of welded borosilicate rods by Bos et al. (2008) suggests that the reliability of glass welds is comparable to that of the main material and that the presence of a weld does not influence the specimen’s strength.

Apart from the \(\hbox {A}_{1}\) and \(\hbox {A}_{2}\) series that were restricted to lengths of max. 500 mm, all other tested specimens failed by buckling. Specimens of the \(\hbox {B}_{2}\) and \(\hbox {C}_{1}\) series (2400 mm long) failed in load values close to the expected critical force by Euler’s formula. The \(\hbox {C}_{1}\) specimens, where post-tensioning was applied, presented a more consistent failure and a narrow load spread. Yet, post-tensioning of the column requires a very precise fit of the tendon to the glass component to increase the carrying capacity of the specimens. Still, the consistent and visible buckling failure, as well as the improved post-breakage behaviour of the column can greatly reduce the imposed safety factors. In this direction, the steel tendon can also be designed and engineered to provide an alternative, built-in load path that can reduce the consequences of failure.

Further work will focus on the development of the top and bottom connections as well as on increasing the safety of the column. For this, the effect of post-tensioning will be further explored and a series of experiments will be conducted to explore in detail the column’s performance.

The presented glass column design will be first applied in the truss elements of a temporary pedestrian 14 m long bridge at the TU Delft campus.