Article

Instantaneous Disturbance Index for Power Distribution Networks

by
María Dolores Borrás-Talavera
*,
Juan Carlos Bravo
and
César Álvarez-Arroyo
Electrical Engineering Department, Escuela Politécnica Superior, Universidad de Sevilla, c/Virgen de África 9, 41011 Sevilla, Spain
*
Author to whom correspondence should be addressed.
Sensors 2021, 21(4), 1348; https://doi.org/10.3390/s21041348
Submission received: 14 January 2021 / Revised: 8 February 2021 / Accepted: 11 February 2021 / Published: 14 February 2021
(This article belongs to the Topic Scientific Advances in STEM: From Professor to Students)

Abstract

:
The stability of power systems is very sensitive to voltage or current variations caused by the discontinuous supply of renewable power feeders. Moreover, the impact of these anomalies varies depending on the sensitivity/resilience of customer and transmission system equipment to those deviations. From any of these points of view, an instantaneous characterization of power quality (PQ) aspects becomes an important task. For this purpose, a wavelet-based power quality indices (PQIs) are introduced in this paper. An instantaneous disturbance index (ITD(t)) and a Global Disturbance Ratio index (GDR) are defined to integrally reflect the PQ level in Power Distribution Networks (PDN) under steady-state and/or transient conditions. With only these two indices it is possible to quantify the effects of non-stationary disturbances with high resolution and precision. These PQIs offer an advantage over other similar because of the suitable choice of mother wavelet function that permits to minimize leakage errors between wavelet levels. The wavelet-based algorithms which give rise to these PQIs can be implemented in smart sensors and used for monitoring purposes in PDN. The applicability of the proposed indices is validated by using a real-time experimental platform. In this emulated power system, signals are generated and real-time data are analyzed by a specifically designed software. The effectiveness of this method of detection and identification of disturbances has been proven by comparing the proposed PQIs with classical indices. The results confirm that the proposed method efficiently extracts the characteristics of each component from the multi-event test signals and thus clearly indicates the combined effect of these events through an accurate estimation of the PQIs.

1. Introduction

The extensive use of power-switching devices for source conditioning, renewable energy supply and motion control in modern industrial applications has detrimental side-effects on power quality, such as increase potential for unacceptable harmonic levels, poor power factor, or unbalanced currents and voltages in power distribution networks. In addition, transients caused by faults and switching events in power systems significantly affect the power-transfer quality of a supply [1,2]. All these undesirable effects cause huge economic losses [3] and require an effective power quality analysis in the grid and affected facilities. Smart sensors proposals are rapidly increasing in response to these new requirements [4,5,6,7,8,9]. Although the first applications were almost exclusively limited to billing, they now include new features related to power quality detection and have a common denominator: they require high processing speed to handle large computer data in a shorter time. In this context it is crucial to provide a small number of parameters and indicators that can effectively characterize all these events and derive from a very fast and efficient analysis tool. This task is the main objective of this work.
The power quality index (PQI) is the summary of waveform distortions in voltage and current from the perfect sinusoids. The PQIs are used to characterize the degree of quality degradation in a quantitative manner. They represent the impacts of non-ideal waveforms on electrical power systems in a compact but expressive manner. Existing indices such as Total Harmonic Distortion (THD), Power factor, Flicker factor, etc. reflect the degree of power disturbance in each of these categories individually, but fail to assess most of the phenomena mentioned together in an exhaustive and concise manner by a single value [10].
Several methods have been applied to research the real-time behavior of controllers, test and protection equipment [11] and fault diagnosis devices [12,13]. All of these applications, together with those mentioned above, have a positive and economic impact on the industry. A measuring device integrated into the system offers the additional characteristic of quantifying the various characteristics that affect power quality and thus identifies any specific aspect that needs attention.
Power quality measurement and analysis has typically been divided between steady-state concerns, such as harmonic distortion, and transient concerns, such as those resulting from faults or switching transients. Fourier analysis has been applied to the first class of problems while Joint Time-Frequency Analysis (JTFA), including wavelets, has traditionally been used for the second class [14].
When using the discrete Fourier transform (DFT) in nonstationary situations, the estimation of a time-varying signal during a specific time interval results in a serious deterioration of measurement accuracy. The effect is equivalent to the frequency deviation of the power system from its nominal value when measuring electrical signals [15,16]. To avoid this problem, the Fourier Transform applied in time segments as the Short-Time Fourier Transform (STFT) determines the frequency contents of a signal in each time window. Nevertheless, the size of the window affects the capacity of multi-resolution capability and the cost of the calculations is high. These deficiencies can be solved by using the Discrete Wavelet Transform (DWT) that also avoids the problems of interference of time and frequency distributions [17]. Besides, the DWT method offers a better time and frequency resolutions for high and low-frequency components, respectively. This method is best for locating disturbances in non-stationary conditions. However, the limitation of the DWT uncertain can be a shortcoming that can be minimized by an appropriate choice of the analyzing wavelet basic function. In this article, the Daubechies40 wavelet offers the best results for the analyzed electrical signals present in power distribution networks.
Traditionally, DWT [18,19,20,21,22,23,24], the generalized S-transform (GST) [25,26,27,28,29,30], the Time-Frequency distributions, and the Short-DFT (SDFT) [31] have been used for the analysis of the transient and time-varying nature of disturbance signals in electric power systems. In particular, power quality indices [32,33,34,35,36,37,38] have been defined using these transforms. Thus, the estimation of standard time-varying PQIs is done based on a proper JTFA [32], adaptive window-based fast generalized S-transform [33], empirical wavelet transform (EWT)-based time-frequency technique [34], cluster analysis of long-term power quality (PQ) data [35], wavelet packet transform [36], load composition rate and Euclidean norm of total harmonic distortions [37], and global harmonic parameters for phasor measurement units [38]. Most of these works use many PQIs in their proposals, for example, the global PQIs introduced in [35] contain up to seven PQI factors. As will be shown later, only two PQIs are used in the present work. Specific treatment of transient events is done in [39], whereas in [37] only stationary distortion is considered. Thus, it is necessary to conceive a measure of power quality in order to capture simultaneously both the “transient” characteristics of disturbance signals in electrical power systems [39] and the stationary ones. Moreover, it must be done with a minimum computational cost and using a single descriptive indicator. Wavelet-based techniques are good candidates for this purpose. However, a method based on empirical wavelet transform will work properly for off-line data processing but not for real-time analysis due to its computational cost [34,40].
Due to their powerful characteristics, in this work, DWT and multiresolution analysis (MRA) are chosen for the joint analysis of the stationary and transient parts of electrical signals. These parts are extracted from a monitoring window to ensure the correct use of the DWT. In this way, the fundamental component of the electrical signal is extracted and the window containing the transient disturbance is processed. Both aspects are subsequently used to construct new DWT based power-quality indices that replace existing counterparts. On the other hand, the main drawback of this method is based on its limitation in the analysis of highly noisy signals. In these noisy conditions, the method has been proven to work properly until the minimum value of 34 dB for the signal-to-noise ratio (SNR) [19], which is more than enough for most of practical PQ events detections in low-voltage AC power distribution networks.
Reference [41] presents an interesting overview of power quality in low-voltage DC distribution networks. This study highlights the most relevant disturbances in DC networks and how they can be accurately characterized by means of power quality indices, some of which have been defined based on DFT. Due to the close relationship between the indices defined in AC power system networks and DC networks, a characterization of PQ in DC networks using the current DWT-based method seems to be interesting and deserves future work. In this possible context, the implementation of the algorithms derived from the present work in smart sensors may provide new functionalities for PQ improvement. However, they could increase the power consumption requirements of such sensors. In this way, reference [42] presents a useful study of the power requirement of functional sensors in a traditional PV system. It is based on Neural Network maximum power point tracking with cloud method and estimates the reduction percentage of power consumption in functional sensors.
In this paper we propose two wavelet-based power quality indices, the Instantaneous Disturbance Index (ITD) and the Global Disturbance Ratio (GDR), which comprehensively assess the power transfer quality of a given supply in steady-state and/or transient situations. The proposed ITD instantly shows the evolution of the PQ. It has the advantage of evaluating the PQ in real-time situations under any conditions and extracting the characteristics of the disturbance for any load in the power distribution networks. In addition, GDR has the advantage of assessing PQ by means of a single value and allows distinguishing between different events, so the GDR can be used as an input in a disturbance classifier. Therefore, the new PQ indices can identify properly practical waveform distortions in power networks. They can also be used to evaluate both the effectiveness and dynamic responses of PQ mitigation equipment in practical applications. In this work, a real-time platform is being developed to experimentally validate the feasibility of the proposed PQI measurement and analysis method.
The rest of this document is organized as follows: In Section 2, a simplified outline of wavelet filter selection criteria is presented. Section 3 briefly describes the DWT-based instantaneous indices used to evaluate PQ. Section 4 shows a detailed summary of the proposed measurement process is shown. In Section 5, results are discussed. The last section draws conclusions from the results.

2. Fundamentals of the Proposed Indices

2.1. Components Signal Estimation

The proposed estimation technique uses DWT and MRA for extracting the fundamental component of the input signal s(t), which can be described by wavelet coefficients [14,24]
s ( t ) = k = 1 2 J a J , k   ϕ J , k ( t ) + j = 1 J k = 1 2 J d j , k   ψ j , k ( t )
where j and k are the wavelet frequency scale and wavelet time scale, respectively, J is the highest j scale, i.e., the lowest frequency band; aJ,k and dJ,k are the wavelet coefficients; and ψ(t) and φ(t) are the mother and scale wavelet functions, respectively. Equations (1)–(3) present the basic concepts of MRA. The aim of MRA is to develop representations of a complex signal f(t) in terms of scaling and wavelet functions.
The digitized version of input signal s(t) is a sequence of n samples, s(n), which can be processed in the same way as the DFT. In addition, the number of DWT levels (decomposition) is limited by the number of the original signal samples, which in turn must be a power of two.
Therefore, signal s(n) can be presented in terms of its frequency components, i.e., coefficient aJ,k, k = 1, …, 2J, is the smoothed version of signal s(n), and coefficients dj,k, k = 1, …, 2J, j = 1, …, J are detailed versions of s(n). They contain the lower and higher-frequency components, respectively [14].
s ( n ) = a J ( n ) + j = 1 J d j ( n )
With
a j ( k ) = n g ( n 2 k ) a j 1 ( k ) d j ( k ) = n h ( n 2 k ) a j 1 ( k )
where aj and dj are the approximation and detail coefficients at level j, g(k) and h(k) are the high pass and low pass filters corresponding to the scaling and wavelet filters. The coefficients have half of the original input data due to the downsampling process.
For extracting the fundamental component of a signal by using MRA, the sampling rate and, so, the number of MRA steps must be specified. If it is assumed that H is the frequency band order with central frequency, ω/(), equal to fundamental frequency and fs is the sampling frequency, the number of MRA steps, J, satisfies the following expression:
f s 2 J = 2 × H
In this work has been assumed that the most important transients occurring in actual situations of Power Distribution Networks (PDN) are captured into a frequency band of 6400 Hz, for fs = 1/TS = 12.8 kHz. It assures accurate results with J = 6.

2.2. Decomposition Structures of MRA Method

MRA method uses a decomposition structure based on Quadrature Mirror Filter (QMF). QMF consists of two complementary filters, one low pass and the other high pass, which disjoin the frequency range into two equal parts. They decompose the input signal into two frequency intervals, the low pass filter output is downsampled and is used as new input of another identical filter pair corresponding to the next decomposition level. This operation is repeated recursively, decomposing the signal into approximation (a) and detail (d) coefficients for various scales.
The coefficients of the scale g and wavelet h filters, and the efficiency of wavelet analysis, are related to the selected mother wavelet. The right selection of the mother wavelet is the main task to obtain the desired results in signal analysis with WMRA. In this work, the selection of the analyzer function is based on the efficiency of the scale and wavelet filters used for this purpose.
The QMF filters frequency response of the first level DWT decomposition is shown in Figure 1. It depicts a comparison of the scale and wavelet filters between the db4, db10, db20, db40, and dmey mother wavelets used on the MRA method. The filters have overlapping frequency bands and energy leakage occurs between the two adjacent bands affecting the obtained coefficients. It is less pronounced with db40 and dmey mother wavelet.

2.3. Wavelet Filters Selection

Several mother wavelets have been evaluated in order to select the most suitable for the specific application of event detection and classification methods. In this paper, the selection of an explicit wavelet is based on the following principles:
-
Minimum frequency leakage of QMF in the first levels of decomposition.
-
Number of filter coefficients.
-
Similarity between classical THD (Total Harmonic Distortion Ratio) with the TWD (Total Wavelet Disturbance Ratio) defined with wavelets.
The main selection criterion is the frequency selectivity. It is based on the magnitude transition zone slope of the frequency response of the wavelet filters. The selected mother wavelet will have better characteristics if the slope of both filters has the highest value and the information dispersion related to the frequency content of the signal will be less. In this way, a greater concentration of energy is obtained in single frequency bands.
A comparison between Fourier and Wavelet analysis is made to select the most appropriated. The STFT has good performance with signals disturbed by harmonics. According to the Parseval theorem, the energy of a signal can be decomposed in terms of the energy of a and d coefficients, the selected mother wavelet will be that allocate the signal energy correctly.
Figure 2a shows a signal that contains three harmonics, the 3rd (7% Urms), the 5th (10% Urms), and the 9th (10% Urms). This signal is chosen to support the selection of the best mother wavelet available. Figure 2b shows the FFT spectrum where the fundamental harmonic has 97.570% of the total signal energy, the 3rd has 0.478% and both the 5th and 9th have 0.976%. Figure 2c also shows as a bar graph the energy percentage of this disturbed signal obtained with various mother wavelets. Table 1 shows the percentage of signal energy achieved with the mother wavelets depicted in the legend of Figure 2c.
Table 2 shows the THD and TWD results calculated, the results are similar excluding bior6.8 and db10 ones.
According to Table 1, the mother wavelets with the best frequency response correctly distribute the energy of the signal according to the FFT spectrum (Figure 2). Therefore, the db40 and dmey wavelets are the best mother wavelets. Since the db40 wavelet has fewer coefficients than the dmey wavelet, the db40 is the mother wavelet with the best performance.

3. Quantitative Formulations of Steady-State and Transient Power Quality Aspects

This formulation is based on the IEC 61000-4-7 standard [43], EN-50160 standard [44] and the IEEE Std 1159™-2009 [45] guidelines, in order to fulfil the essential requirements and to define the characteristics of the supplied voltage and the most common disturbances.

3.1. DWT-Based Disturbance Ratio

The Total Harmonic Distortion ratio (THD) for single-phase networks (or polyphase balanced networks) has been defined traditionally as [43,46]
T H D = h = 2 H S k 2 S 1 100 H = f m 2 f 0
T H D = S 2 S 1 2 S 1 100
where S denotes RMS value of signal s(n), S1 denotes fundamental component of s(n), and Sk the k component of s(n). Using the MRA tool, S is given by
S = S a J 2 + j J S d j 2
Here SaJ, is the RMS value of the N samples signal aJ(n) in the lowest frequency band J, where the fundamental component S1 is included. {Sdj} is the set of RMS values of dj(n) signal in the higher frequency band, or wavelet-level lower than or equal to the scaling level J. Then, the Total Wavelet Disturbance ratio TWD [47] is defined as
T W D = j J S d j 2 S a J 100

3.2. DWT-Based Instantaneous Disturbance Ratio

The Instantaneous Transient Disturbance ratio (ITD(n)), the transient version of TWD, is defined (9) in terms of the time-scale distribution of the MRA components:
I T D ( n ) = j J d j 2 ( n ) A J 100
where AJ is the fundamental energy component defined as:
A J 2 = 1 N n = 1 N a J 2 ( n )
It can be seen that SaJ is identical to AJ.
The definition of the ITD(n) can be interpreted as a “time-varying” power quality evaluation determined by the time-frequency localized energy ratio of the disturbance events to the fundamental frequency energy.
As an instantaneous quantity, the proposed ITD(n) index can reveal the time-varying characteristics of the transient disturbance for assessment purposes.
The time-varying signature can be quantified as a single number, as in the case of steady-state disturbances. Therefore, a “transient-interval average” of the ITD(n), <ITD>, can be defined over a sample interval N as follows:
I T D = 1 N n = 1 N I T D ( n )
Note that <ITD> is almost identical to THD when only steady-state disturbances are presented in the signal.
The non-stationary events duration is a very relevant parameter to be considered. It can be measured with high precision by the wavelet procedure used in this work. Then a Global Disturbance Ratio, GDR, can be defined,
G D R = ( 1 + T 0 T ) I T D
where T0 is the duration of the transient disturbance and T is the time interval window used. The selection of the time interval (T0) can be determined by the time index of the first maximum peak value of the ITD(n), t0, and the time index of the last maximum peak value of the ITD(n), t0 + T0. Only if steady-state disturbances are present in the signal, GDR = <ITD>, otherwise GDR is greater than <ITD>.
Consequently, the proposed index GDR is the transient-interval average, <ITD>, plus its magnitude weighted by a term related to the event duration.
A loaded power network with sinusoidal voltages yields an ideal null GDR. Conversely, a high value of GDR would indicate a high level of steady-state and/or transient disturbances, with the contribution of each event aspect well defined and measured. Note that the proposed index GDR presents the advantage over the THD of distinguishing transients and stationary events. The duration of the disturbance plays a significant role in the GDR index.

4. Measurement Process

4.1. Developed Platform

In this work, a developed platform is used to test the effectiveness of the proposed indices under common real-time working conditions (Figure 3). This procedure permits the emulation of actual power systems. In this context, the proposed instantaneous indices are suitable.
The developed system consists of a signal generator that allows the design of any kind of disturbance. This signal is amplified, conditioned and applied to a real load. Finally, the voltage and current are measured on the load side and processed in a power quality analyzer.
Matlab® software has been used to program a virtual signal generator, called Sigen, which allows a complete configuration of the signals required for testing. Sigen mainly generates a pattern based on the parameters defined by the user; thus, steady-state and/or transient-state disturbances can be modelled. The Graphical user interface of single-phase Sigen is shown in Figure 4.
The processes of Sigen are performed to complete the effective generation of electric signals, as follows.
  • First, electrical inputs signals are defined and the user sets their parameters.
  • Second, signals according to these specifications are built.
  • Finally, the designed signals are sent to a file or to the data acquisition board (DAQ).
Sigen is designed to program disturbances as described in IEEE standard 1159-09 for monitoring electric power quality [45].
The design is based on generating single or three-phase voltages and line currents. Generated data sets are obtained from a host PC in data files with the American Standard Code for Information Interchange format compatible with the most popular data analysis tools.
The host PC is equipped with the NI USB-6259; it is a 16-Bit High-Speed M Series Multifunction DAQ for USB. It acquires eight differential inputs. Analog inputs are converted with 16 bits of resolution sampled at 1.25 MS/s. Voltage and current sensors are built with Hall Effect voltage and current transducers, type LV25-P and LA25-NP, respectively. Low-level voltage signals proportional to the phase-neutral voltages are available.
At the final stage, an amplifier section increases the voltage signals up to the grid voltage level. A decisive request remains on the amplifier section since it must ensure accurate and constant gain and phase shift overall bandwidth required. A Pacific Power Source Model 320 is used as a power amplifier to fulfill all the proposed requirements (output voltage up to ±600 peak volts; maximum output power: 1.2 kVA; bandwidth (30–5 kHz) at full power; THD < 0.2%).
Disturbed voltage signals at the grid level are generated for studying Power Quality Events in several types of loads.
The generated voltage signals are used to simulate a power system with actual voltage sources and arbitrary loads. It can process polyphase sinusoidal voltages added with simple or multiple disturbances.
The power-quality analyzer is a virtual device that processes the signal data file from an A/D converted connected to the signal conditioner (Figure 5). A control program developed in MATLAB® diagnoses quality aspects of the input signals, such as frequency stability, distortion level, symmetry of three-phase signals (balance between phases R, S and T), and others that can be inferred from the graphical user interface of Figure 4.
In order to carry out this diagnosis, the system can measure and present/display the graphs (with its time evolution):
  • Instantaneous network frequency, following its changes at intervals of measurement of one cycle, considering deformed signals and with adding noise.
  • Harmonics, represented in phasor form using two bar charts, one for magnitudes and another for phases.
  • Instantaneous PQI and coefficients of power quality indices (percent), and a presentation of the data corresponding to the signals.
  • DWT coefficients with a representation of the wavelet level selected by the user.
  • Three-phase signals of voltage and current, or in its place, their respective fundamental symmetrical components, i.e., the fundamental components of positive, negative and zero sequences.
Furthermore, the PQ System analyzer computes power quantities in Wavelet and Fourier domain specified by IEEE standard 1459–2010 [46].
The developed platform and the proposed indices can be further used in real-time for both monitoring and detecting faults in power networks [20] and electrical machinery [48]. By means of a signal-based fault diagnosis method, the proposed novel indices can be applied to loads such as induction motors, power converters, and mechanical components.

4.2. PQI Measurements

Different kinds of power quality disturbances are applied through the power voltage amplifier to linear and nonlinear loads. In these loads, voltages and currents are taken by the PQ System Analyzer.
For the voltage quality assessment, instantaneous frequency measurement is performed which enables synchronization between the signal period and the sampling sequence.
For the considered voltage and current windows specified by IEC standard 61000-4-30 [49], time-frequency-based quality aspects are calculated by the DWT. For the case of 12.8-kHz sampling rate in the Sigen system, Table 3 summarizes the frequency band information for different wavelet analysis levels. The db40 mother wavelet is applied in MRA of the voltage and current signals.
According to Equations (5), (6), (8), (9), (11) and (12) the PQIs are computed. The PQ indices have been tested on a variety of stationary, non-stationary single-phase signals as well as balanced or unbalanced three-phase signals.
To measure properly disturbances with a higher duration than the considered window, the PQ system analyzer provides a GDR history tool to save stored data of the GDR index.
The fundamental component of the grid voltage presented in all the used test signals is distorted by harmonics and/or non-stationary events, in accordance with both, the IEEE standard 1159-2009 [45] and the European standard EN-50160 [44].

5. Illustrative Results

To show the effectiveness of GDR and <ITD>, TWD, and THD indices are also calculated and the result obtained has been compared in two examples sets. In all of them, the grid voltage waveform contains a fundamental component of 230 Vrms, 50 Hz of nominal frequency, and stationary and/or transient disturbances. In the first set, a group of signals with single disturbances and almost identical THD index are considered. In the second set, complex signals with more significant and combined disturbances are studied.

5.1. Voltages Waveform with Similar THD

Several disturbed voltage waveforms extracted from the developed platform are analyzed. In particular, the considered signals are three voltage sags and two swells with different duration and amplitude, three oscillatory transients with distinct frequency and duration, a steady-state distorted voltage with three harmonics (5th, 7th, and 9th with relative amplitudes depicted in the FFT spectrum of Figure 6) and a flicker disturbance. Some of them are depicted in Figure 7 and they all only have in common a similar THD value.
These voltage signals are applied to linear and nonlinear loads, and the resulting load currents are analyzed in our PQ System Analyzer too. The corresponding voltage FFT spectra are shown in Figure 7. The ITD(t) of the signals shown in Figure 6 are respectively depicted in Figure 8. The first ITD(t) at the left top of Figure 8 shows two peak values: 3.1% at 31.1 ms and 2.7% at 146.2 ms. The second ITD(t) at the right top shows two peak values: 3.3% at 21.2 ms and 2.5% at 136 ms. The peak values in both signals are associated with the depth/crest of the corresponding sag/swell. The ITD(t) attaching to oscillatory transient of Figure 8 shows a peak value of 44.27% at 53 ms. In this context, the peak values indicate that the oscillatory transient is a more severe event than the harmonic distortion. However, it presents the shortest time duration and the highest frequency content of the five disturbances (FFT spectra of Figure 7). The ITD(t) for steady-state conditions do not offer any new relevant information over the THD, nevertheless <ITD> is almost identical to THD (Table 4). In this case, the error between both quantities is less than 0.5%.
Table 4 provides the quantities obtained for all the examples discussed in terms of their respective duration (T0), Vrms value and time-frequency based transient power quality indices. It can be seen that THD is almost the same for all disturbed signals even if they correspond to different classes of disturbances. TWD is similar to THD in those signals in which the frequency bands are far from the fundamental energy component. On the contrary, in those with the frequency components near to the fundamental, the values are very different and the duration of the disturbance does not make any substantial difference. Instead, GDR and <ITD> assessments are more consistent with the energy content of these disturbance signals.
The ITD(t) (Figure 8) shows the instantaneous character of the disturbance noting the relevance of any suddenly introduced change. Instead, its averaged energy over the observation window is considered by the GDR. Furthermore, the GDR permits to distinguish between different disturbances and can be used for classification purposes. In particular, the GDR differentiates the proposed disturbances, with almost the same THD, by giving importance to both, the amplitude and the duration of the disturbance. This index offers the advantage to indicate clearly the most relevant of them, as can be seen in Table 4 for any kind of the disturbances numbered as “1”. So transient events are perfectly characterized by this procedure. Nevertheless, the studied sag and swell signals have the same frequency contents and are undistinguished by all the indices, so the RMS value has to be considered as an assisting index.

5.2. Disturbances Combination in Voltage Waveforms

In practical situations, a PQ event usually consists of a combination of singular disturbances, most of them treated in case A. Therefore, a set of complex disturbed signals with more severe and combined effect are studied.
Figure 9a depicts the ITD(t) corresponding to a pronounced sag. It shows two peak value: 5.5% at 56.25 ms and 3.3% at 147.25 ms. Figure 9b shows this index for a combination of the mentioned sag and a steady-state distorted voltage with five harmonics (3rd, 5th, 7th, 9th, and 11th and Vrms equal to 10 V, 17 V, 7 V 13 V, and 3 V, respectively). The ITD(t) resulting from a steady-state distorted voltage only with the five harmonics is provided in Figure 9c. In addition, Figure 9d shows this index for a combination of the same steady-state voltage and an important transient oscillation. The ITD(t) of a voltage disturbed only with this single transient is shown in Figure 9e. It has a peak value of 30% at 127 ms.
In this case, the waveform offers more relevant changes than the previous set of examples because more substantial disturbances are present. When the signal is disturbed with two events, both are evinced in ITD(t) graph.
The PQ indices obtained are presented in Table 5. By comparing the values obtained, the GDR index remarks the effect of the disturbances combination. As it can be observed from Table 5, the proposed index is the only one capable to indicate clearly the accumulative effect of the combined events in complex signals. Although the GDR index has not the additivity property, it performs the indication by significantly increasing its relative value when distinct disturbances are present.

6. Conclusions

The motivation for this work stemmed from the growing need for a more effective analysis of power quality in electrical systems and equipment. In this way, the main contribution of this research is the introduction of a novel wavelet-based single indicator, designated global disturbance ratio (GDR) that has been tested on real signals to address an integral assessment of the electrical network PQ. The objective of these test is to guarantee the applicability of such index to smart network sensors in particular, and to PQ monitoring in general. To this end, a PQ System Analyzer based on wavelet techniques is developed, turning out to be an effective device to verify the behavior of the proposed indices.
The GDR is based on an instantaneous index ITD(t), which is also introduced, and considers two quality aspects of the electrical signal: steady-state power quality relative to harmonic level, and the non-stationary index relative to oscillatory transients or sudden amplitude changes in the signal.
In the initial theoretical stage of signal analysis it is remarkable the mother wavelet selection procedure used to guarantee the most accurate frequency decomposition of the voltage signal under steady-state and non-stationary events.
The applicability of the GDR and ITD(t) is illustrated for typical source-load configurations. The proposed PQIs have been tested on single-phase stationary and non-stationary complex signals, as well as three-phase balanced and unbalanced signals.
Finally, the ITD(t) and GDR indices are a powerful tool for detecting and monitoring non-stationary signal components and they can extract relevant characteristics. In particular, the GDR index may be applied as the input of a classifier. In this sense, the authors are working on the physical implementation of an intelligent sensor based on a DSP, which provides the proposed PQIs. This guideline deserves future research.

Author Contributions

M.D.B.-T. Conceived and developed the idea of this research, generated the data, performed the simulations, designed the whole structure of the experimental device, and wrote most of the paper; J.C.B. Contributed to the methodology and wrote some of the paper; C.Á.-A. contributed to the development of the experimental device and the simulations and wrote some of the paper. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Universidad de Sevilla (VI Plan Propio de Investigación y Transferencia) under grant 2020/00000596.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Montaño, J.-C.; Bravo, J.-C.; Borrás, M.-D. Joint Time–Frequency Analysis of the Electrical Signal. In Power Quality: Mitigation Technologies in a Distributed Environment; Moreno-Muñoz, A., Ed.; Springer London: London, UK, 2007; pp. 41–72. ISBN 978-1-84628-772-5. [Google Scholar]
  2. Chawda, G.S.; Shaik, A.G.; Shaik, M.; Padmanaban, S.; Holm-Nielsen, J.B.; Mahela, O.P.; Kaliannan, P. Comprehensive Review on Detection and Classification of Power Quality Disturbances in Utility Grid with Renewable Energy Penetration. IEEE Access 2020, 8, 146807–146830. [Google Scholar] [CrossRef]
  3. Sharma, A.; Rajpurohit, B.S.; Singh, S.N. A review on economics of power quality: Impact, assessment and mitigation. Renew. Sustain. Energy Rev. 2018, 88, 363–372. [Google Scholar] [CrossRef]
  4. Viciana, E.; Alcayde, A.; Montoya, F.; Baños, R.; Arrabal-Campos, F.; Manzano-Agugliaro, F. An Open Hardware Design for Internet of Things Power Quality and Energy Saving Solutions. Sensors 2019, 19, 627. [Google Scholar] [CrossRef] [Green Version]
  5. Artale, G.; Caravello, G.; Cataliotti, A.; Cosentino, V.; Di Cara, D.; Dipaola, N.; Guaiana, S.; Panzavecchia, N.; Sambataro, M.G.; Tinè, G. PQ and Harmonic Assessment Issues on Low-Cost Smart Metering Platforms: A Case Study. Sensors 2020, 20, 6361. [Google Scholar] [CrossRef] [PubMed]
  6. Thongkhao, Y.; Pora, W. A low-cost Wi-Fi smart plug with on-off and Energy Metering functions. In Proceedings of the 2016 13th International Conference on Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), Chiang Mai, Thailand, 28 June–1 July 2016; IEEE: Piscataway, NJ, USA; pp. 1–5. [Google Scholar]
  7. Yaemprayoon, S.; Boonplian, V.; Srinonchat, J. Developing an innovation smart meter based on CS5490. In Proceedings of the 2016 13th International Conference on Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), Chiang Mai, Thailand, 28 June–1 July 2016; IEEE: Piscataway, NJ, USA, 2016; pp. 1–4. [Google Scholar]
  8. Sun, Q.; Li, H.; Ma, Z.; Wang, C.; Campillo, J.; Zhang, Q.; Wallin, F.; Guo, J. A comprehensive review of smart energy meters in intelligent energy networks. IEEE Internet Things J. 2015, 3, 464–479. [Google Scholar] [CrossRef]
  9. Albu, M.M.; Sănduleac, M.; Stănescu, C. Syncretic use of smart meters for power quality monitoring in emerging networks. IEEE Trans. Smart Grid 2016, 8, 485–492. [Google Scholar] [CrossRef]
  10. Sharon, D.; Montano, J.; Lopez, A.; Castilla, M.; Borras, D.; Gutierrez, J. Power Quality Factor for Networks Supplying Unbalanced Nonlinear Loads. IEEE Trans. Instrum. Meas. 2008, 57, 1268–1274. [Google Scholar] [CrossRef] [Green Version]
  11. Montano, J.; Leon, C.; Garcia, A.; Lopez, A.; Monedero, I.; Personal, E. Random Generation of Arbitrary Waveforms for Emulating Three-Phase Systems. IEEE Trans. Ind. Electron. 2012, 59, 4032–4040. [Google Scholar] [CrossRef]
  12. Jin, H.; Titus, A.; Liu, Y.; Wang, Y.; Han, Z. Fault Diagnosis of Rotary Parts of a Heavy-Duty Horizontal Lathe Based on Wavelet Packet Transform and Support Vector Machine. Sensors 2019, 19, 4069. [Google Scholar] [CrossRef] [Green Version]
  13. Gao, Z.; Cecati, C.; Ding, S.X. A survey of fault diagnosis and fault-tolerant techniques-part I: Fault diagnosis with model-based and signal-based approaches. IEEE Trans. Ind. Electron. 2015, 62, 3757–3767. [Google Scholar] [CrossRef] [Green Version]
  14. Borras, D.; Castilla, M.; Moreno, N.; Montano, J.C. Wavelet and neural structure: A new tool for diagnostic of power system disturbances. IEEE Trans. Ind. Appl. 2001, 37, 184–190. [Google Scholar] [CrossRef]
  15. Wen, H.; Guo, S.; Teng, Z.; Li, F.; Yang, Y. Frequency Estimation of Distorted and Noisy Signals in Power Systems by FFT-Based Approach. IEEE Trans. Power Syst. 2014, 29, 765–774. [Google Scholar] [CrossRef]
  16. Lopez, A.; Montano, J.; Castilla, M.; Gutierrez, J.; Borras, M.D.; Bravo, J.C. Power System Frequency Measurement Under Nonstationary Situations. IEEE Trans. Power Deliv. 2008, 23, 562–567. [Google Scholar] [CrossRef] [Green Version]
  17. Jeong, J.; Williams, W.J. Kernel design for reduced interference distributions. IEEE Trans. Signal Process. 1992, 40, 402–412. [Google Scholar] [CrossRef]
  18. Borrás, M.D.; Montaño, J.C.; Castilla, M.; López, A.; Gutiérrez, J.; Bravo, J.C. Voltage index for stationary and transient states. In Proceedings of the Mediterranean Electrotechnical Conference-MELECON, Valletta, Malta, 26–28 April 2010; University of Seville: Sevilla, Spain, 2010; pp. 679–684. [Google Scholar]
  19. Borrás, M.D.; Bravo, J.C.; Montaño, J.C. Disturbance Ratio for Optimal Multi-Event Classification in Power Distribution Networks. IEEE Trans. Ind. Electron. 2016, 63, 3117–3124. [Google Scholar] [CrossRef]
  20. Bravo, J.C.; Borras, M.D.; Torres, F.J. Development of a smart wavelet-based power quality monitoring system. In Proceedings of the 2018 International Conference on Smart Energy Systems and Technologies (SEST), Sevilla, Spain, 10–12 September 2018; IEEE: Piscataway, NJ, USA, 2018; pp. 1–6. [Google Scholar]
  21. Lu, S.-D.; Sian, H.-W.; Wang, M.-H.; Liao, R.-M. Application of Extension Neural Network with Discrete Wavelet Transform and Parseval’s Theorem for Power Quality Analysis. Appl. Sci. 2019, 9, 2228. [Google Scholar] [CrossRef] [Green Version]
  22. Khokhar, S.; Asuhaimi, A.; Zin, M.; Memon, A.P.; Safawi Mokhtar, A. A new optimal feature selection algorithm for classification of power quality disturbances using discrete wavelet transform and probabilistic neural network. Measurement 2017, 95, 246–259. [Google Scholar] [CrossRef]
  23. Wang, J.; Xu, Z.; Che, Y. Power Quality Disturbance Classification Based on DWT and Multilayer Perceptron Extreme Learning Machine. Appl. Sci. 2019, 9, 2315. [Google Scholar] [CrossRef] [Green Version]
  24. Costa, F.B. Boundary Wavelet Coefficients for Real-Time Detection of Transients Induced by Faults and Power-Quality Disturbances. IEEE Trans. Power Deliv. 2014, 29, 2674–2687. [Google Scholar] [CrossRef]
  25. Bravo-Rodríguez, J.C.; Torres, F.J.; Borrás, M.D. Hybrid Machine Learning Models for Classifying Power Quality Disturbances: A Comparative Study. Energies 2020, 13, 2761. [Google Scholar] [CrossRef]
  26. Kumar, R.; Singh, B.; Shahani, D.T.; Chandra, A.; Al-Haddad, K. Recognition of Power-Quality Disturbances Using S-Transform-Based ANN Classifier and Rule-Based Decision Tree. IEEE Trans. Ind. Appl. 2015, 51, 1249–1258. [Google Scholar] [CrossRef]
  27. Shafiullah, M.; Abido, M.A.; Abdel-Fattah, T. Distribution grids fault location employing ST based optimized machine learning approach. Energies 2018, 11, 2328. [Google Scholar] [CrossRef] [Green Version]
  28. Wang, H.; Wang, P.; Liu, T. Power quality disturbance classification using the S-transform and probabilistic neural network. Energies 2017, 10, 107. [Google Scholar] [CrossRef] [Green Version]
  29. Reddy, M.V.; Sodhi, R. A modified S-transform and random forests-based power quality assessment framework. IEEE Trans. Instrum. Meas. 2018, 67, 78–89. [Google Scholar] [CrossRef]
  30. Tang, Q.; Qiu, W.; Zhou, Y. Classification of Complex Power Quality Disturbances Using Optimized S-Transform and Kernel SVM. IEEE Trans. Ind. Electron. 2020, 67, 9715–9723. [Google Scholar] [CrossRef]
  31. Heydt, G.T.; Fjeld, P.S.; Liu, C.C.; Pierce, D.; Tu, L.; Hensley, G. Applications of the windowed FFT to electric power quality assessment. IEEE Trans. Power Deliv. 1999, 14, 1411–1416. [Google Scholar] [CrossRef]
  32. Lin, T.; Domijan, A. On power quality indices and real time measurement. IEEE Trans. Power Deliv. 2005, 20, 2552–2562. [Google Scholar] [CrossRef]
  33. Biswal, M.; Dash, P.K. Estimation of time-varying power quality indices with an adaptive window-based fast generalised S-transform. IET Sci. Meas. Technol. 2012, 6, 189. [Google Scholar] [CrossRef]
  34. Thirumala, K.; Umarikar, A.C.; Jain, T. Estimation of Single-Phase and Three-Phase Power-Quality Indices Using Empirical Wavelet Transform. IEEE Trans. Power Deliv. 2015, 30, 445–454. [Google Scholar] [CrossRef]
  35. Jasiński, M.; Sikorski, T.; Kostyła, P.; Leonowicz, Z.; Borkowski, K. Combined cluster analysis and global power quality indices for the qualitative assessment of the time-varying condition of power quality in an electrical power network with distributed generation. Energies 2020, 13, 2050. [Google Scholar] [CrossRef] [Green Version]
  36. Morsi, W.G.; El-Hawary, M.E. Wavelet Packet Transform-Based Power Quality Indices for Balanced and Unbalanced Three-Phase Systems Under Stationary or Nonstationary Operating Conditions. IEEE Trans. Power Deliv. 2009, 24, 2300–2310. [Google Scholar] [CrossRef]
  37. Jo, S.; Son, S.; Park, J. On Improving Distortion Power Quality Index in Distributed Power Grids. IEEE Trans. Smart Grid 2013, 4, 586–595. [Google Scholar] [CrossRef]
  38. Granados-Lieberman, D. Global harmonic parameters for estimation of power quality indices: An approach for PMUs. Energies 2020, 13, 2337. [Google Scholar] [CrossRef]
  39. Shin, Y.; Powers, E.J.; Grady, M.; Arapostathis, A. Power quality indices for transient disturbances. IEEE Trans. Power Deliv. 2006, 21, 253–261. [Google Scholar] [CrossRef]
  40. Sahani, M.; Dash, P.K.; Samal, D. A real-time power quality events recognition using variational mode decomposition and online-sequential extreme learning machine. Meas. J. Int. Meas. Confed. 2020, 157, 107597. [Google Scholar] [CrossRef]
  41. Barros, J.; de Apráiz, M.; Diego, R.I. Power quality in DC distribution networks. Energies 2019, 12, 848. [Google Scholar] [CrossRef] [Green Version]
  42. Chang, S.; Wang, Q.; Hu, H.; Ding, Z.; Guo, H. An NNwC MPPT-Based energy supply solution for sensor nodes in buildings and its feasibility study. Energies 2019, 12, 101. [Google Scholar] [CrossRef] [Green Version]
  43. IEC 61000-4-7. Electromagnetic Compatibility (EMC)—Part 4-7: Testing and Measurement Techniques—General Guide on Harmonics and Interharmonics Measurements and Instrumentation, for Power Supply Systems and Equipment Connected Thereto; International Electrotechnical Commission: Geneva, Switzerland, 2008. [Google Scholar]
  44. EN 50160: Voltage Characteristics of Electricity Supplied by Public Distribution Network; British Standards: London, UK, 2010.
  45. IEEE Recommended Practice for Monitoring Electric Power Quality; IEEE Std 1159-2019 (Revision of IEEE Std 1159-2009); Institute of Electrical and Electronics Engineers: Piscataway, NJ, USA, 2019; pp. 1–98.
  46. IEEE Standard Definitions for the Measurement of Electric Power Quantities under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced Conditions; IEEE Std 1459-2010 (Revision of IEEE Std 1459-2000); Institute of Electrical and Electronics Engineers: Piscataway, NJ, USA, 2010; pp. 1–50.
  47. Morsi, W.G.; El-Hawary, M.E. Reformulating Power Components Definitions Contained in the IEEE Standard 1459–2000 Using Discrete Wavelet Transform. IEEE Trans. Power Deliv. 2007, 22, 1910–1916. [Google Scholar] [CrossRef]
  48. Gritli, Y.; Zarri, L.; Rossi, C.; Filippetti, F.; Capolino, G.; Casadei, D. Advanced Diagnosis of Electrical Faults in Wound-Rotor Induction Machines. IEEE Trans. Ind. Electron. 2013, 60, 4012–4024. [Google Scholar] [CrossRef]
  49. IEC 61000-4-30:2015. Electromagnetic Compatibility (EMC)—Part 4-30: Testing and Measurement Techniques—Power Quality Measurement Methods; International Electrotechnical Commission: Geneva, Switzerland, 2015. [Google Scholar]
Figure 1. Comparative frequency response of mother wavelets.
Figure 1. Comparative frequency response of mother wavelets.
Sensors 21 01348 g001
Figure 2. Voltage signal with harmonics: (a) Instantaneous representation, (b) FFT spectrum, (c) distribution of the energy percentage of the signal according to the coefficients of the mother wavelets.
Figure 2. Voltage signal with harmonics: (a) Instantaneous representation, (b) FFT spectrum, (c) distribution of the energy percentage of the signal according to the coefficients of the mother wavelets.
Sensors 21 01348 g002
Figure 3. Developed system scheme: Voltage generator with preset disturbances, power amplifier, and signal conditioner, load and Power Quality Analyzer.
Figure 3. Developed system scheme: Voltage generator with preset disturbances, power amplifier, and signal conditioner, load and Power Quality Analyzer.
Sensors 21 01348 g003
Figure 4. Graphical user interface of the Sigen system.
Figure 4. Graphical user interface of the Sigen system.
Sensors 21 01348 g004
Figure 5. Graphical user interface of the power quality (PQ) System Analyzer.
Figure 5. Graphical user interface of the power quality (PQ) System Analyzer.
Sensors 21 01348 g005
Figure 6. FFT spectra for several signals used on case A.
Figure 6. FFT spectra for several signals used on case A.
Sensors 21 01348 g006
Figure 7. Single-phase voltage disturbances with similar THD. (a) Voltage sag1. (b) Voltage swell1. (c) Harmonic disturbances. (d) Flicker disturbance. (e) Transient1 disturbance.
Figure 7. Single-phase voltage disturbances with similar THD. (a) Voltage sag1. (b) Voltage swell1. (c) Harmonic disturbances. (d) Flicker disturbance. (e) Transient1 disturbance.
Sensors 21 01348 g007
Figure 8. Instantaneous Transient Disturbance ratio index ITD(t) of voltage disturbances corresponding to Figure 5.
Figure 8. Instantaneous Transient Disturbance ratio index ITD(t) of voltage disturbances corresponding to Figure 5.
Sensors 21 01348 g008
Figure 9. Instantaneous Transient Disturbance ratio index ITD(t) of voltage disturbances combination.
Figure 9. Instantaneous Transient Disturbance ratio index ITD(t) of voltage disturbances combination.
Sensors 21 01348 g009
Table 1. Energies (%) of voltage signal decomposition shown in Figure 2.
Table 1. Energies (%) of voltage signal decomposition shown in Figure 2.
f(Hz)a6
0–100
d6
100–200
d5
200–400
d4
400–800
d3
800–1600
d2
100–200
d1
3200–6400
db1097.61420.43781.15610.79120.00070.00000.0000
db2097.57190.4610 1.09660.87060.00000.00000.0000
sym2097.57050.5844 0.97450.8706 0.0000 0.00000.0000
db3097.57040.4616 1.05500.9130 0.0000 0.00000.0000
bior6.897.23150.7903 1.19310.7817 0.0035 0.00000.0000
db4097.56990.46731.02570.93710.00000.00000.0000
dmey97.57050.49051.01160.92740.0000 0.00000.0000
Table 2. Total Harmonic Distortion (THD) and Total Wavelet Disturbance Ratio (TWD) of voltage signal decomposition shown in Figure 2.
Table 2. Total Harmonic Distortion (THD) and Total Wavelet Disturbance Ratio (TWD) of voltage signal decomposition shown in Figure 2.
THDTWD
db10
TWD
db20
TWD
sym20
TWD
db30
TWD
bior6.8
TWD
db40
TWD
dmey
15.779715.633515.775115.779815.780116.874115.781815.7796
Table 3. Frequency bands and harmonics of six levels of the Discrete Wavelet Transform (DWT).
Table 3. Frequency bands and harmonics of six levels of the Discrete Wavelet Transform (DWT).
LevelFreq. Band (Hz)Odd Band Harmonics
7 (d1)3200–640063rd–127rd (odd num.)
6 (d2)1600–320033rd–63rd (odd num.)
5 (d3)800–160017th–31st (odd num.)
4 (d4)400–8009th, 11th, 13th, 15th
3 (d5)200–4005th, 7th
2 (d6)100–2003rd
1 (a6)DC-1001st
Table 4. Summary of Power Quality Indices for the case A.
Table 4. Summary of Power Quality Indices for the case A.
Sag1 Sag2Sag3HarmonicsTransient1Transient2Transient3FlickerSwell1Swell2
T0 (ms)120.6280.3160.22082.8957.4228.120120.6280.62
Vrms (V)212.67218.35220.65230.54230.53230.56230.42230.54251.63244.18
THD6.88266.88576.88216.86086.84106.88526.84696.85896.87846.8742
TWD0.64910.65150.70786.86076.84076.88486.84254.60670.65640.6610
<ITD>0.32790.33290.35526.43973.86883.30182.23954.04940.32840.3409
GDR0.52570.47650.46286.43975.47234.24982.55444.04940.52650.4783
Table 5. Summary of Power Quality Indices for case B.
Table 5. Summary of Power Quality Indices for case B.
SagSag + HarmonicsHarmonicsHarmonics + TransientsTransients
T0 (ms)100.62100.62062.8162.81
Vrms200.30201.51231.36232.14230.79
THD16.896620.271010.880413.67168.2782
TWD1.259711.099910.880413.67058.2766
<ITD>0.717010.053610.102512.29014.1376
GDR1.077815.111810.102516.14995.4370
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Borrás-Talavera, M.D.; Bravo, J.C.; Álvarez-Arroyo, C. Instantaneous Disturbance Index for Power Distribution Networks. Sensors 2021, 21, 1348. https://doi.org/10.3390/s21041348

AMA Style

Borrás-Talavera MD, Bravo JC, Álvarez-Arroyo C. Instantaneous Disturbance Index for Power Distribution Networks. Sensors. 2021; 21(4):1348. https://doi.org/10.3390/s21041348

Chicago/Turabian Style

Borrás-Talavera, María Dolores, Juan Carlos Bravo, and César Álvarez-Arroyo. 2021. "Instantaneous Disturbance Index for Power Distribution Networks" Sensors 21, no. 4: 1348. https://doi.org/10.3390/s21041348

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop