Thermal Science 2010 Volume 14, Issue 2, Pages: 521-531
https://doi.org/10.2298/TSCI1002521X
Full text ( 3612 KB)
Cited by


An evaluation of the BFD curve based upon wood crib fires performed in an ISO 9705 room

Xu Qiang (Nanjing University of Science and Technology, Nanjing, China)
Griffin Gregory J. (CSIRO, Manufacturing and Materials Technology, Highett, Victoria, Australia)
Jiang Yong (University of Science and Technology of China, Hefei, China)
Jin Cong (Nanjing University of Science and Technology, Nanjing, China)

The BFD curve fitting method of Barnett is adopted to study the compartment temperature-time curves for a series of wood crib fires in an ISO 9705 room. The nominal fire sizes were 0.15 MW, 0.25 MW, 0.5 MW, and 1.0 MW. The cribs were positioned at the corner or the center of the floor of the room. The temperatures within the compartment were measured using two thermocouple trees with 10 thermocouples on each tree; these measured the compartment temperature from floor to ceiling. No flashover occurred during the tests, and the compartment temperature can be well described by a two-zone model. BFD curve fitting was performed for all 20 temperature-time curves in the upper and lower zones of the compartment for each test. The fitting error is evaluated for all tests. This empirical model needs more tests to verify and optimize.

Keywords: compartment temperature, wood crib fire, ISO 9705 room, BFD curve