Elsevier

Energy Procedia

Volume 57, 2014, Pages 2676-2685
Energy Procedia

Energy and Exergy Analysis of Water-LiBr Absorption Systems with Adiabatic Absorbers for Heating and Cooling

https://doi.org/10.1016/j.egypro.2014.10.279Get rights and content
Under a Creative Commons license
open access

Abstract

Solar energy can be used to produce cold through absorption systems. In this study, the energy and exergy analysis on a single effect water-LiBr absorption facility is presented. The work is carried out for heating and cooling applications. Performance parameters are the coefficient of performance and exergy efficiency. The influence of operating temperatures on such parameters is included. An analysis of individual components is also presented. The most noticeable effect is observed for the case of exergy efficiency for absorber and generator. This parameter increases with an increase of absorption temperature. The opposite effect is observed when the generation temperature increases. Results obtained allow the identification of parameters that may influence the exergy efficiency of the adiabatic absorption system. The first candidate to optimize is the absorber, due to the lowest value of exergy efficiency obtained among all components of the system. For adiabatic absorbers, the recirculation ratio emerges as a new parameter. The solution heat exchanger is also susceptible to optimization.

Keywords

Adiabatic Absorption
Water-Lithium bromide
exergy analysis

Cited by (0)

Selection and/or peer-review under responsibility of ISES.